Welcome to our website
  • head_banner_01

As protection of over-voltage, under voltage, phase failure, phase sequence and phase unbalance. When the power supply is abnormal, turn off power supply to protect the equipment

Short Description:

Used in air conditioning units, elevator machine room, pumps, fans and other motor control applications, as protection of over-voltage, under voltage, phase failure, phase sequence and phase unbalance. When the power supply is abnormal, turn off power supply to protect the equipment.


Product Detail

Product Tags

product_icon

Relay FAQ

The relay is not conducting
1) When the relay should be turned on, measure the input voltage. If the voltage is lower than the required operating voltage, it indicates that there is a problem with the line in front of the SSR input; if the input voltage is higher than the required operating voltage, check the polarity of the power supply and if necessary be corrected.

2) Measure the input current of the SSR. If there is no current, it means that the SSR is open, and the relay is faulty; if there is current, but it is lower than the action value of the relay, there is a problem with the line in front of the SSR and must be corrected.

3) Check the input part of the SSR, measure the voltage across the output of the SSR, if the voltage is lower than 1V, it indicates that the line or load other than the relay is open and should be repaired; if there is a line voltage, it may be the load short circuit, causing the current to be too large. Relay failed.

product_icon

Function

Categories Voltage Control Relay
Rated control supply voltage AC220V. AC380V DC12V DC24V~240V 50/60Hz
Rated power consumption AC:≤1.5VA DC:≤1W
Delay range 0.1s~100h
Setting accuracy ≤5%
Repeat acuracy ≤0.2%
Repeat power-on interval ≥200ms
Atitude ≤2000m
Contact configuration capacity(A) 1C/O,2C/O l6A, 1C/O+1 intant c/O, 3C/O 8A
IP Class IP 20
Contact capacity 1 C/O, 2 C/O, 1C/O+1 instant C/O, 3C/O
product_icon

Applications

Used in air conditioning units, elevator machine room, pumps, fans and other motor control applications, as protection  of  over-voltage,  under  voltage, phase failure, phase sequence and phase unbalance. When the power  supply is abnormal, turn off power supply to protect the equipment.

product_icon

Features

Built-in microprocessors, true RMS voltage measurement, voltage measurement accuracy 5 1%. Measuring frequency 45Hz~65Hz, button setting, LCD display voltage and fault information, protection can be turned on or off. Check phase voltage value by button, with N-phase phase failureprotection. DIN rail mounting.

product_icon

Technical Data

Rated supply voltage DC12V, AC/DC 24V~240V 50/60Hz
Rated power consumption ≤1W
Delay range 0.1s ~ 100h multi-range adjustment
Setting accuracy ≤5%
Repeat accuracy ≤0.2%
Repeat power-on interval ≥200ms
Electrical Life 105
Mechanical life 106
Altitude ≤2000m
Contact configuration capacity(A) 1C/O:16A ,2C/O:16A,3C/O:8A,2C/0+1 instant C/O:8A+ 16A
IP Class IP 20
Class of pllution
Use category AC-15
Contact capacity Ue/le AC240V/1.5A
Contact capacity 1C/0 ,2C/O,3C/O,2C/0+1 instant C/O
DIN rail Standard width 35mm(IEC/EN60715)
Allowable relative humidity ≤50%(40°C) (No condensation )
Short circuit protector type RT36-00 5A
product_icon

Wiring Diagram

details (3)
product_icon

Dimension

details (1)
details (2)
product_icon

factory

factory
factory
factory
factory
factory
factory
factory
factory
product_icon

certification

certification
certification
certification
certification
certification
certification
certification
certification

  • Previous:
  • Next:

  • Write your message here and send it to us